Thermopile
Burner Ports
Electrode
Thermocouple
1. Remove the control panel.
2. The pressure test taps are located on the valve. The taps are located on the gas valve front
face. The inlet is marked ‘INand the outlet is marked ‘OUT’. (See Fig.1)
3. Loosen the set screw inside the tap with a ⅛” (3 mm) wide flat screwdriver.
4. Connect a ¼” (6 mm) rubber tube to the tap post and a manometer.
5. Verify the readings obtained are within specs (as shown on the appliance rating plate)
6. Be sure to tighten the set screw inside the tap after you are finish taking pressure readings.
7. Check for leaks.
CHECKING INLET AND OUTLET GAS PRESSURE
CHECKING AND ADJUSTING PILOT
The pilot flame should have the characteristic
as shown in the illustration below. The flame
should not have yellow tips but should engulf
the thermocouple and thermopile. It can be
adjusted by turning the screw marked “pilot”
on the control valve.
Fig. 1
CONVERTIBLE PILOT ORIFICE
The pilot assembly is convertible to the type of
gas being used. Simply unscrew the body by
using a 7/16” (11 mm) wrench and turn ¼
open - then push the small metal tab across to
the other side of the body and retighten. Call
your local Authorized Archgard Dealer to
purchase the correct fuel conversion kit
for your gas appliance.
7/16”
(11 mm)
WRENCH
(HERE)
OUT (manifold)
IN (inlet)