31-DVI33N 16
The 31-DVI33N
requires two flexible
gas flue liners:
Flue Collar (inlet) -
3” (76 mm) diameter
Flue Collar (outlet) -
3” (76 mm) diameter
Caution: Only two 3” (76 mm) “FLEX-MASTER” Model GA gas flex vent liners (or approved equivalent)
and a vent terminal is approved for use with this appliance.
Approved vent terminals are:
Archgard terminal. Part # 999-INS-TK
Simpsons Dura-Vent terminal. Part # 980, 923GK (adaptor with flashing) or 991 (high wind
cap). If you are using “Dura-Vent” vertical termination cap, follow the instructions provided
with the “Dura-Vent” cap.
NO OTHER VENTING SYSTEM OR COMPONENTS MAY BE USED.
This appliance is designed to attach to two 3” (76 mm) co-linear aluminum flex gas liners running the full
length of the chimney. The flue length must be a minimum of 8’ (2.44 M) and a maximum of 40’ (12.2 M)
(The exhaust vent restrictor provided with this appliance must only be used by installing it onto
the front of the baffle on natural gas units with vent heights over 18’ (5.4 M). Also refer to the follow-
ing page for details. The minimum flue size is 4” x7” (100 mm X 178 mm).
Masonry chimneys may take various contours which the flexible liner will accommodate, however, keep
the flexible liner as straight as possible, avoiding unnecessary bending but at all times keep a minimum of
3” (76 mm) inside bend radius.
The Air Intake Flex Liner must be connected to the inlet air collars of the termination cap and the appli-
ance. The Exhaust Flex Liner must be connected to the exhaust collars of the termination cap and the
appliance. (DO NOT MIX-UP THESE CONNECTIONS).
The Air intake and Exhaust connections are marked on the gas appliance. See Fig. 1.
CAUTION: To ensure that the venting path is not accidentally obstructed or punctured, the
damper of the host fireplace must be permanently disabled by either complete removal of the
damper, or welding it in its “open” position. Temporarily disabling the damper with braces,
VENTING INSTRUCTIONS
WARNING: Operation of this heater when not connected to a properly installed and main-
tained venting system can result in carbon monoxide (CO) poisoning and possible death.
The appliance must not be connected to a chimney flue serving a separate solid fuel
burning appliance.
Exhaust
Fresh Air Intake
The 31-DVI33N showing the Fresh Air Intake and Exhaust locations.
These connections are labeled for you.
Fig. 1