Instructions for use with Archgard vertical termination cap. Part # 999-INS-TK
Install the termination cap being sure to provide sufficient space (around and on top) so as not to
impede the flow of air, both into and out of the cap. This cap is only to be used for non combusti-
ble installations. Do not recess into the top of the chimney.
1. Mark each end of one liner with Air Intake”.
2. Mark each end of the second liner with “Exhaust”.
3. Pull the liner through the chimney.
4. Install the flashing. Do Not bend or cut the flashing in any way.
5. Seal and attach the liner marked Air Intake” to the vent terminal pipe marked Air Intake” with the collar
clamp provided.
6. Seal and attach the liner marked “Exhaust” to the vent terminal pipe marked “Exhaust” with the collar clamp
provided.
7. Seal and attach the end of the flex marked “Air Intake” to the collar marked “Air Intake” on the appliance
with the collar clamp provided with the unit.
8. Install exhaust vent restrictors provided with the unit on Natural Gas appliances only. .
Seal and attach
the end of the flex marked “Exhaust” to the collar marked “Exhaust” on the appliance.
9. Caulk all joints using a high temperature sealant such as milpac. DO NOT USE SILICONE SEALANTS. Use
of silicon sealants voids the warranty of the pilot assembly.
NOTE: The vertical termination cap must be sealed to the liner with suitable high temperature sealant and with the
hose clamps fasteners provided. The liners must form a complete connection from the appliance
flue collars to the
vertical termination cap.
VENTING INSTRUCTIONS 999-INS-TK
The minimum flue (chimney) size required to run the two 3” (76 mm) is 4” x7” (100 mm X 178 mm)
Front view of
DV Insert
Exhaust
Collar
Exhaust
Air Intake
Collar
3” (76 mm)
Flex Liner
Fresh Air
Intake
Min. vent height 10’(2.54 M)
Max. vent height 40’ (12.2 M)
Vertical Termination cap
Part # 999-INS-TK
Place Vent Restrictor
in the position shown
when operating with
NATURAL GAS with a
vent over 18’ (5.5 Me-
ters)
Firebox baffle with
restrictor
Firebox baffle with-
out restrictor
Page view 16